Y_EC_COE_SdoWrite

Image

The function block provides the user program with an accessor to write SDO data to the EtherCAT (CoE) slave or master object dictionary. The data is accessed by object index and sub-index.

Parameters

* Parameter Data Type Description Default
VAR_IN_OUT
E Record ANY Provides the data to be written. The input Length indicates the number of bytes to be written.
VAR_INPUT
B Execute BOOL Upon the rising edge of the Execute input, all other inputs are read and the function block becomes operational. If an input needs to be modified, the value will have to be changed and the Execute input will have to be re-triggered. FALSE
E NetworkID WORD Network ID of the EtherCAT master. A value of 0 is not allowed and will be treated as the default (1). WORD#1
E StationAddress WORD EtherCAT station address of the slave/master. The EtherCAT Master has StationAddress 0. WORD#0
E Index WORD Index of the object that is to be written. WORD#0
E Subindex BYTE Subindex of the object that is to be written. BYTE#0
E Length UDINT Number of bytes which are to be written from the object. The variable connected to the VAR_IN_OUT must have at least this length, otherwise an error message will be generated. If a value of 0 is passed, then the full size of the connected VAR_IN_OUT Record data type is used by default. UDINT#0
E Timeout UINT Timeout value in ms. A value of 0 is not allowed and will be treated as the default (5000). UINT#5000
E CompleteAccess BOOL This parameter defines whether only a single sub-index, or the entire object is to be written. FALSE
VAR_OUTPUT
B Done BOOL The Done output is set to TRUE when the commanded action has completed successfully. If another function block takes control before the action is completed, the Done output will never become TRUE. This output is reset when Execute becomes FALSE.
B Busy BOOL For function blocks with Execute input, the Busy output is set to TRUE upon the rising edge of the Execute, and set to FALSE when Done, CommandAborted or Error outputs becomes TRUE. In the case of a function block with an Enable input, Busy indicates that the function block is operating, but may not be ready to provide valid outputs.
B Error BOOL The Error output is set to TRUE if an error has occurred during the operation of the function block. The output is cleared when the Execute or Enable input becomes FALSE.
E ErrorID UINT The ErrorID output provides the identifier of the error when there is an active error in the function block execution. The output is cleared when the Execute or Enable input becomes FALSE.

Notes

Error Description

See the Function Block ErrorID List.

Notes on Error IDs for this function block:

Example 1

In the following example we want to change the value of the speed loop gain to 41Hz.
The station address of the device can be found in the settings tab of the servo-node:
Image

The index of the parameter can be found in the CoE Data tab of the servo-node:
Image

The value of 410 is written in order to set the parameter to 41Hz:
Image

Example 2

In the following example the user wants to command an EEPROM write to all parameters.

Image


 