Initialization actions on PLC start of IC92xx controller

This section lists the actions performed when the iC92xx controller powers up or when the user forces a start.

Note: There is "no distinction" between power on and stop/warm-start.
Step Warm Start from power on or Reboot from iCube Engineer or WBM Cold Start*
1 Resets configured EtherCAT network.
  1. All devices are requested to go to EtherCAT state --> PREOP
  2. servopack identification data is read, incl. encoder resolution etc
  3. all devices are requested to go to EtherCAT state --> OP

same behavior
2 Initializes non-retain data.
Initializes all data, both retain and non-retain.
3 Clears servo alarms.
same behavior
4 Runs warm start event task one time
Runs cold start event task one time
5 Runs cyclic tasks
same behavior

* Cold start can be requested by the user in iCE. Cold start may also happen automatically when a project is downloaded to a controller that is at factory reset condition.

 