Establish communications to the controller at default settings
| Version Number | Description |
|---|---|
| 1.0 | This version shows only the very first phase of a controller startup. |
Application note shows first steps to get the bare controller working at factory default condition. iCube Engineer 2022.9 and Slioiec
1. Supported Components
| Component Name | Version |
|---|---|
| iC9200 series | ≥ 2022.9 |
| iCube Engineer | ≥ 2022.9 |
2. Supported Libraries
No Libraries required
| Version Number | Description |
|---|---|
| 1 |
|
3. Solution details
3.1 Physical Connections
- Check front panel switch settings
- S1 and S2 OFF (to the left)
- Wire 24Vdc as per manual and apply power
- Main LED goes from Red to flashing yellow to
- Physically disconnect the Slicebus io from the controller
- Physically disconnect the EtherCAT cable from port X1
3.2 Factory Default
- If the controller is new in box then these following steps are not required
- Reset controller to factory default if required. Hold Operating Mode Switch at position MR during power up and release when main LED turns orange (yellow)
- Programming and all settings are deleted. Firmware is unchanged.
- LED will be orange (yellow) when Operating Mode Switch is at position ST and green at position RN
- Clear firmware if required. Hold Operating Mode Switch at position MR during power up for 30+ seconds
- Firmware reverts to factory setting. Programming and all settings are deleted.
3.3 Communication between PC and Controller
- Set IP address of computer NIC to 192.168.1.2 and subnet mask 255.255.255.0
- Win-R > ncpa.cpl > open connection > TCP/IPv4 > Properties
- Connect Ethernet cable between port ETH-X3 and computer NIC
- Point url to controller ip address 192.168.1.1
- Accept any warnings / advanced and proceed even if browser indicates unsafe.
- Enter the Username admin and Password listed on front panel
- Result: Web UI (WBM) appears in the browser
3.4 Firmware
- Determine the current firmware level
- Determine the required firmware level
- Use the newest firmware if this is a new application
- Match to existing controller firmware level if this is replacement or OEM machine
- Acquire the required firmware file from www.yaskawa.com
- File extension *.raucb and file size > 150MB
- Update the firmware by Administration> Firmware Update > Browse > Start Update
- Expect automatic reboot after 1 minute followed by communication error
- Expect WBM login prompt after 2 minutes
3.5 iCube Project Communication
- Start new iCube Engineer project without template
- Set the project IP address range. Project > Settings > IP subnet > IP range. Start IP address 192.168.1.1. End IP address 192.168.1.1
- Add controller to project. Select Device > Add selected device to project (button)
- Possible prompt to Enter a new password for safety-related access
- If the controller has safety, define safety password such as ‘yaskawa1’ when prompted
- Verify Operating Mode Switch at position RN (up)
- Download empty project. PLANT > Project > right click controller in the tree > write and start project
- Prompt to save project.
- Enter project filename or accept suggested name.
- Prompt to enter user name and password
- Enter the Username admin and Password listed on front panel
- Status LED solid green
The controller is now running an empty project with the target firmware and is communicating to the PC.