Effect of MRESET vs Archive delete vs Reset type1/2 on iC9200 series

Version Number Description
1.0 Initial version


This application note show effect of different reset types of the controller.

1. Supported Components

Component Name Version
iC9200 series ≥ 2024.3
iCube Engineer ≥ 2024.3

2. Solution details

The table below shows the effect of different reset types on different controller parameters.

MRESET Delete Archive Factory Reset Type 1 Factory Reset Type 2
Project Unloaded for the current session and reloaded after the power cycle Deleted  Deleted  Deleted 
Retain Variable Not Retained Not Retained Not Retained Not Retained
System and Services Remain Remain Reset to default Reset to default
IP Address Remain Remain Resets to 192.168.1.1 Resets to 192.168.1.1
Notification Logs Remain Remain Deleted Deleted
Dates and Time Remain Remain Remain Remain
Users & Password Remain Remain Deleted Deleted
Identity store - OPC UA server/client certificate Remain Regenerated Regenerated Regenerated
Trust store - OPC UA client certificate Remain Deleted after reboot Deleted Deleted
Firmware Remain Remain Remain Resets to the delivery/original firmware version
Licenses Remain Remain Remain
Remain

 


This help information is valid for iCube Engineer Online Help 2025.6